New F-gas rules: SF6 in MV switchgear from 2026 and heat pump bans from 2027

Regulation (EU) 2024/573 of the European Parliament and of the Council of 7 February 2024 replaced Regulation (EU) No 517/2014. It entered into force on 11 March 2024 (twenty days after publication in the Official Journal on 20 February 2024) and applies directly. For the electrical sector two blocks of rules matter most: bans on putting into operation switchgear that uses fluorinated greenhouse gases (Article 13(9)–(20)) and bans on placing on the market heat pumps and air conditioners using high-GWP refrigerants (Annex IV).
SF6 switchgear: the ban timetable
Sulphur hexafluoride (SF6) has a GWP of 24,300 (100-year horizon) according to Annex I. Article 13(9) prohibits the putting into operation of switchgear using fluorinated greenhouse gases in the insulating or breaking medium as follows:
- from 1 January 2026 — medium voltage switchgear for primary and secondary distribution up to and including 24 kV;
- from 1 January 2028 — switchgear from 52 kV up to and including 145 kV and up to 50 kA short-circuit current, with gases of GWP 1 or more;
- from 1 January 2030 — MV switchgear above 24 kV up to and including 52 kV;
- from 1 January 2032 — HV switchgear above 145 kV or above 50 kA short-circuit current, with gases of GWP 1 or more.
For MV switchgear up to 24 kV the ban is already in force. In new transformer substations and MV switchrooms up to 24 kV, F-gas-free solutions are used unless a derogation applies.
Derogations that must be documented
The regulation provides for several situations in which the ban in paragraph 9 does not apply:
- moving switchgear already operating in the EU to another site is not “putting into operation” (paragraph 10);
- if, in a procurement procedure during the first 2 years after the MV ban date, no bids or only bids from a single manufacturer of F-gas-free switchgear were received, switchgear with a medium of GWP below 1,000 is allowed; after that period, only if no bid for F-gas-free switchgear was received (paragraph 11); a medium with GWP of 1,000 or more only if no bid for switchgear with GWP below 1,000 was received (paragraph 12);
- the operator proves that the order was placed before 11 March 2024 (paragraph 14);
- extension of existing switchgear where devices using a lower-GWP gas are not compatible and would require replacing the entire switchgear (paragraph 15).
An operator relying on a derogation keeps the documentation for at least 5 years (paragraph 16) and, for paragraphs 11, 12, 14 and 15, notifies the competent authority of the Member State (paragraph 17). Spare parts may be fitted to existing switchgear provided that neither the GWP nor the amount of gas in the equipment increases (paragraph 18).
Servicing, leak checks and labelling of switchgear
- From 1 January 2035, only reclaimed or recycled SF6 may be used to maintain or service switchgear, unless it is proved that it cannot be used for technical reasons or is unavailable for an emergency repair (Article 13(7)).
- Switchgear is exempt from leak checks if it has a tested leakage rate below 0.1% per year (and is labelled accordingly), has a pressure or density monitoring device with an automatic alert, or contains less than 6 kg of Annex I fluorinated gases (Article 5(1)).
- Switchgear containing F-gases is placed on the market with a label (Article 12), and gas recovery at decommissioning is done by certified persons (Articles 8 and 10).
Heat pumps and air conditioning: Annex IV bans
Annex IV prohibits the placing on the market of certain equipment. Key dates for the installation market:
- from 1 January 2027 — self-contained (monoblock) heat pumps and air conditioners up to 12 kW with F-gases of GWP 150 or more (point 8(b)) and self-contained units above 12 kW up to 50 kW with GWP 150 or more (point 8(d));
- from 1 January 2027 — split air-to-water heat pumps up to 12 kW with GWP 150 or more (point 9(b));
- from 1 January 2029 — split air-to-air systems up to 12 kW with GWP 150 or more (point 9(c)) and split systems above 12 kW with GWP 750 or more (point 9(e));
- from 1 January 2032 — self-contained units up to 12 kW with any F-gas (point 8(c)); from 2033 — split systems above 12 kW with GWP 150 or more (point 9(f)); from 2035 — split systems up to 12 kW with any F-gas (point 9(d)).
Most of these bans contain the proviso “except if required to meet safety requirements at the site of operation”. Points 8(b) and 8(d) add that where safety requirements at the site of operation do not allow a refrigerant with GWP below 150, the limit is 750 (in point 8(c) — where they do not allow alternatives to F-gases). For comparison, HFC-32 (R32), a common heat pump refrigerant, has a GWP of 675 in Annex I — above the 150 threshold but within the 750 limit. This exception can be used only if the operator proves that safety requirements at the location do not permit a lower-GWP refrigerant (Article 13(19)(a)). Manufacturers in these segments are therefore moving to low-GWP refrigerants, including natural ones.
Important for wholesalers: the ban concerns placing on the market, i.e. first making available on the EU market. Under Article 13(19), equipment placed on the market before the ban date may be installed later, but the operator must be able to prove this and keep the evidence for at least 5 years (paragraph 20). Keep delivery records for 2026 stock.
Servicing existing heat pumps
Since 1 January 2026, F-gases with GWP of 2,500 or more may not be used to maintain or service air conditioning equipment and heat pumps (Article 13(4)). Until 1 January 2032, however, reclaimed (properly labelled) or recycled gases recovered from such equipment may still be used.
- MV switchgear up to 24 kV with SF6 — ban on putting into service. Servicing of air conditioning and heat pumps: ban on F-gases with GWP ≥ 2,500 (except reclaimed or recycled).
- Monoblock heat pumps and air conditioners up to 50 kW and air-to-water split heat pumps up to 12 kW with GWP ≥ 150 — ban on placing on the market.
- Switchgear 52–145 kV (up to 50 kA) with gas of GWP ≥ 1.
- Air-to-air split systems up to 12 kW with GWP ≥ 150; split systems above 12 kW with GWP ≥ 750.
- MV switchgear above 24 kV up to 52 kV.
- HV switchgear above 145 kV or above 50 kA (GWP ≥ 1); self-contained equipment up to 12 kW with any F-gas; end of servicing with reclaimed gases of GWP ≥ 2,500.
- 2033Split systems above 12 kW with GWP ≥ 150.
- 2035Split systems up to 12 kW with any F-gas; from 1 January 2035 switchgear may be serviced only with reclaimed or recycled SF6.
What this means for electrical businesses
- For MV substation projects up to 24 kV, require F-gas-free switchgear from suppliers or a documented basis for a derogation.
- When extending existing SF6 switchgear, check the compatibility condition in paragraph 15 and the duty to notify the authority.
- In heat pump distribution, plan stock with 1 January 2027 in mind and keep proof of the placing-on-the-market date.
- Work on refrigerant circuits and gas recovery from switchgear is carried out by persons certified under Article 10.
Standards and legal sources
This article is for information only. The applicable regulations and standards and the manufacturer's documentation prevail.